Temperature > Double stage or Neutral Zone > Panel mounting 32*74 - Gamme IC
 
IC 915 Double stage controller for temperature
IC 915, IC 915/R, IC 915/P, IC 915/V-I IC 915 controllers have two points of intervention only and can be used for temperature (IC 915), relative humidity (IC 915/R) and pressure (IC 915/P) control, provided for ONOFF operation. Depending on models, they may have an input for PTC/NTC thermostatic probes or for Pt100/Tcj/Tck probes, EWHS280/300/310 humidity probes, for EWPA007/030 pressure transducers, for 0/4..20 mA, 0..1/5/10 V current and voltage signals (selectable with a parameter). The values measured by the probes are displayed with three and a half digits and a minus sign. All models have TTL connections that enable the controllers to be used with Copy Card, the quick programming accessory. IC 915LX The IC 915LX version includes a connection for TelevisSystem , or alternatively for networks with ModBUS protocol.
Technical Data
----------
Frontal protection IP 65
----------
Container plastic resin PC+ABS UL94V0, polycarbonate glass, thermoplastic resin keys
----------
Dimensions 32x74 mm, depth 60 mm
----------
Mouting panel mounting,
cut out 29x71 mm (+0.2/0.1mm)
----------
Connections screw terminals for <2.5mm
----------
Usage temperature -5...55C
----------
Storage temperature -30...85C
----------
Usage environment humidity 10...90% RH
----------
Storage environment humidity 10...90% RH
----------
Serial TTL port for Copy Card and Televis system
----------
Display 3 digits plus sign
----------
Precision above 0.5% of bottom scale + 1 digit
----------
Consumption 3 VA (115/230 V model), 1.5 VA (12 V model)
----------
Resolution 1C (F)
----------
Power supply 230, 115 Vac or 12 Vac/cc 10%, 50/60Hz
----------

IC 915 - ELIWELL controllers